Outdoor prefabricated substation (European type)
Rated voltage: 12KV
Rated capcacity: 30-2000KVA
Propose: Outdoor pre-installation、 lightning protection and monitoring、supports ring network / radial power supply、can be unmanned、modular design、shortens construction period
Temperature: -25°C~+40°C、Altitude<1000m
Standards: IEC 62271-200、IEC 60076、IEC 61439、IEC 60529
YB()-12/0.4 KV - 华通大图
YB()-12/0.4 KV - 华通大图
Application & Technical Parameters
Service conditions

1. The altitude shall not exceed 1000m;

2. Ambient temperature: - 25 ° C ~ + 40 ° C;

3. Relative humidity: the daily average value shall not be greater than 95%, and the monthly average value shall not be greater than 90%;

4. Installation site: a place without fire, explosion hazard, conductive dust, chemical corrosive gas and violent vibration. If the above conditions are exceeded, the user can negotiate with our company.


Type meaning

华通型号说明.png

Main technical parameters

Technical parameters of load switch

No.

Name

Unit

Load switch
     FN12-12

Vacuum load switch
     FZN12-12

1

Rated voltage

KV

10

2

Maximum operating voltage

KV

12

3

Rated frequenc

HZ

50

4

Rated current

HZ

630

5

Rated breaking current

A

630

6

Thermal stability current(effective value)

KA/S

20/2

20/4

7

Dynamic stable current

KA

50

50

8

Short circuit making current

KA

50

50

9

 Full load breaking times

20

10000

10

Mechanical life

2000

10000

 

11

 

1min power frequency withstand voltage (phase to phase and to ground)

 

KV

 

42

 

42

 

12

 

Lightning impulse voltage(phase to phase and to ground)

 

KV

 

75

 

75


Technical parameters of high voltage fuse


Model

Rated voltage(KV)

Rated current(A)

Breaking current(KA)

Melt rated current(A)

British model

Domestic model

SDL❊J

 

12

40

31.5

6.3,10,16,20,25,31.5,40

SFL❊J

XRNT-12

12

100

31.5

50,63,71,80,100

SKL❊J

 

12

125

31.5

125


Technical parameters of Low voltage circuit break

Model

Release form

Rated current of release (A)

On-off capacityKA(AC380V)

DW15-630

Thermoelectric magnetic or electronic type

315, 400, 630

40

DW15-1000

600,800,1000

50

DW15-1600

1600

50

DW15-2500

1600,2000,2500

60

CW1-2000

Intelligent

630,800,1000,1250,1600,2000

65(80)

CW1-3200

2000,2500,3200

100

Legend of technical scheme

Scheme No.

01

02

03

 

Single line diagram of main circuit

华通图片.png 

 华通图片.png

 华通图片.png

Purpose

Terminal type
     Cable incoming /1 outgoing line

Terminal type
     incoming line

Terminal type
     overhead incoming line

Cabinet type

HXGN-12

HXGN-12

HXGN-12

Selection of primary equipment

 

 

Vacuum circuit breake
     VS1,ZN28

 

 

 

Load switch
     FN,FZN,FLN

1

1

1

Disconnector
     GN

 

 

 

Fuse  XRNT

3

3

3

Fuse  RN2

 

 

 

Lightning arrester  HY5W

3

3

3

Live display  GSN

1

1

1

Current transformer
     LZZBJ

 

 

 

Voltage transformer
     JDZ

 

 

 

Scheme No.

04

05

06

 

Single line diagram of main circuit

华通图片.png 

华通图片.png 

 华通图片.png

Purpose

Terminal type
     Vacuum circuit breake
     incoming line

Terminal type incoming line metering  / 1 outgoing line

Terminal type
     Cable incoming /1 outgoing line/metering

Cabinet type

XGN66-12

HXGN-12

HXGN-12

Selection of primary equipment

 

Vacuum circuit breake
     VS1,ZN28

1

 

 

Load switch
     FN,FZN,FLN

 

1

1

Disconnector
     GN

2

 

 

Fuse  XRNT

 

3

3

Fuse  RN2

 

3

3

Lightning arrester  HY5W

3

3

3

Live display  GSN

1

1

1

Current transformer
     LZZBJ

2

2

2

Voltage transformer
     JDZ

 

2

2

Scheme No.

                07

                    08

                      09

Single line diagram of main circuit

                华通图片.png

 华通图片.png

 华通图片.png

Purpose

Terminal type incoming line metering / Pt / 1 outgoing line

Terminal type incoming line metering / Metering / 1 outgoing line

Terminal type  circuit breaker Incoming/ Metering  

Cabinet type

HXGN-12

HXGN-12

XGN66-12

Selection of primary equipment

 

Vacuum circuit breake
     VS1,ZN28

 

 

1

Load switch
     FN,FZN,FLN

1

2

 

Disconnector
     GN

1

 

2

Fuse  XRNT

3

3

3

Fuse  RN2

3

3

3

Lightning arrester  HY5W

3

3

3

Live display  GSN

1

1

1

Current transformer
     LZZBJ

2

2

4

Voltage transformer
     JDZ

2

2

2

                       Scheme No.

                         10

                     11

                            12

 

Single line diagram of main circuit

 华通图片.png

华通图片2.png 

 华通图片3.png

                           Purpose

Terminal type  circuit breaker Incoming/PT/1 outgoing line

Terminal type
     1 outgoing line/
     2 outgoing line

Terminal type incoming line metering/2 outgoing line

                             Cabinet type

HXGN66-12  HXGN-12

HXGN-12

HXGN-12

Selection of primary equipment

 

Vacuum circuit breake
     VS1,ZN28

1

 

 

Load switch
     FN,FZN,FLN

1

3

2

Disconnector
     GN

3

1

 

Fuse  XRNT

3

6

6

Fuse  RN2

3

 

3

Lightning arrester  HY5W

3

3

3

Live display  GSN

1

1

1

Current transformer
     LZZBJ

2

2

2

Voltage transformer
     JDZ

2

 

2

Substation structure diagram


华通尺寸图.png

Ordering instructions

The following information shall be provided when ordering:

1. Model and quantity of substation;

2. Model and quantity of transformer;

3. HV and LV primary wiring scheme and models and parameters of main components;

4. Material and color of shell.

华通尺寸图.png