Normal service conditions of switchgear as follows: | |
Ambient temperature: | |
Maximum | +40°C |
Maximum 24 hour average | +35°C |
Minimum (according to minus 15 indoor classes) | -5°C |
Ambient humidity: | |
Daily average relative humidity | less than 95% |
Monthly average relative humidity | less than 90% |
Earthquake intensity | less than 8 degree |
Height above sea level | less than 2000m |
This product should not be used under conditions of fire, explosion, earthquake and chemical corrosion environments.
SN | ITEM | Particulars | |
1 | Electrical Data | Rated Voltage | 220~690V |
2 | Rated Frequency | 50/60Hz | |
3 | Connection type | 3 Phase 4 Wire | |
4 | Rated Capacity | 50kvar~5000kvar | |
5 | Capacitors | Type | 480V,3 ph,50/60Hz (Cylindrical) |
No.of Steps | ≤36 steps | ||
Configuration | According to capacity | ||
6 | Reactors | Install reactors | Optional |
Reactance Rate | 7%,14% optional | ||
7 | APFC Relay | Function | Automatically step switching |
Steps | 36 Stage microprocessor based | ||
8 | Switchgear Details | Incomer | HRC Fuse Or MCCB |
Step outgoing | Contactors,Thyristor,IGBT | ||
9 | Enclosure Details | Material | 8MF Profile |
Application | Indoor free standing, floor mounted | ||
Cable Entry | Bottom or Top | ||
Painting | RAL7035 | ||
Dimensions(mm) | 1000*1000*2200 | ||
Protection Class | IP3X | ||

Product code: | A (mm) | B (mm) | C (mm) | D (mm) |
GGJ 606 | 600 | 600 | 450 | 556 |
GGJ 608 | 600 | 800 | 450 | 756 |
GGJ 806 | 800 | 600 | 650 | 556 |
GGJ 808 | 800 | 800 | 650 | 756 |
GGJ 1006 | 1000 | 600 | 850 | 556 |
GGJ 1008 | 1000 | 800 | 850 | 756 |
GGJ 1208 | 1200 | 800 | 1050 | 756 |
Remakes: Dimensions of actual products is usually according to different customer requirements