English Russian Spanish Portuguese French Arabic
HomeProductsLow voltage Switchgear

GGD

Indoor fixed type Low Voltage Switchgear
Rated voltage: 400V
Rated current: 630-7500A
Propose: Electric energy distribution、 circuit control、 fault protection、 operation monitoring
Temperature: -5°C~+40°C、Alititude<2000m
Standards: IEC 61439-1、IEC 61439-2
GGD - 华通大图
GGD - 华通大图2
GGD - 华通大图5
GGD - 华通大图3
GGD - 华通大图4
GGD - 华通大图
GGD - 华通大图2
GGD - 华通大图5
GGD - 华通大图3
GGD - 华通大图4
Application & Technical Parameters
Type meaning

华通型号说明.png

Service conditions

Normal service conditions of switchgear as follows:

Ambient temperature:

Maximum

+40°C

Maximum 24 hour average

+35°C

Minimum (according to minus 15 indoor classes)

-5°C

Ambient humidity:

Daily average relative humidity

less than 95%

Monthly average relative humidity

less than 90%

Earthquake intensity

less than 8 degree

Height above sea level

less than 2000m

This product should not be used under conditions of fire, explosion, earthquake and chemical corrosion environments.


Main Technical specification

Item

Unit

Data

Rated voltage

V

400 / 690

Rated insulation voltage

V

690/1000

Rated frequency

Hz

50 / 60

Rated main bus bar current

A

max:>7500A    

min:630-7500A

Rated short time withstand current of main bus bar (1s)

kA

50/80

Rated short time peak withstand current of main bus bar

kA

105/176

Rated distribution bus bar current

A

1000

Degree of protection


IP30,IP40


Normal dimension of GGD switchgear

Product code:

A (mm)

B (mm)

C (mm)

D (mm)

GGD606

600

600

450

556

GGD608

600

800

450

756

GGD806

800

600

650

556

GGD808

800

800

650

756

GGD1006

1000

600

850

556

GGD1008

1000

800

850

756

GGD1208

1200

800

1050

756

Remakes: Dimensions of  actual products is usually according to different customer requirements